By using multi compressors on each chiller, unloading characteristics and part load
performance are outstanding. Integrated part load value (IPLV) is a part load
performance indicator as outlined in ARI Standard 550/590-1998. The IPLV rating
compares the performance of different chillers under identical conditions. When the
IPLV is listed in EER (Energy Efficiency Ratio), a higher EER will indicate that the chiller's
overall performance is better.
The chillers have a reputation for a compact design and small footprint. A small
footprint can save installation costs by minimizing the size of the concrete mounting
pad or reduces the amount of structural steel if the unit is mounted on the rooftop.
The chillers are designed with quiet scroll compressors. Fans are selected for good
performance and lower sound levels. The attention to detail with sound is critical in the
design. Small issues such as refrigerant piping, supports for piping, securing
components to the structure are all important to making a quiet product. We proudly
publish our sound performance.
Quiet Operation
Excellent Part Load Performance
Compact Design with Small Footprint
4
GREE Central Air Conditioners
Utilizing new scroll compressor technology, the chillers meet or exceed the
performance requirements of ASHRAE 90.1. All system components are selected for
optimum performance, including the condenser coil areas and evaporator sizes.
High Efficiency Full Load Operation
3.2 Standard Specifications
GREE has provided the latest technology in controlling the chillers. The new controller
provides auser friendlyenvironment for the operator. The control logic is designed
to provide maximum efficiency, to help provide continuing operation in unusual
operating conditions through proactive controls, and to provide a history of conditions
to aid in problem resolutions. Perhaps the greatest benefit is the Protocol for
integrating with your building automation system (BAS).
Superior Controls
Compressors
These rugged hermetic compressors are constructed with an integral cast iron frame,
cast iron scrolls, three Teflon impregnated bearings, and three oil filtration devices for
each compressor. One to thity-two compressors can run, depending on the load of
the system, resulting in excellent Part-load efficiency. Each refrigerant circuit has
specially designed oil and gas equalization lines to control oil migration.
The design also offers radial and axial compliance, a large internal volume for liquid
handling, a removable suction screen, and a rotary dirt trap and oil screen. In
addition, the compressor is self-compensating for wear, handles moderate liquid
slugging, and inherently yields high efficiency.